How do I connect to an AC10 using RS485 Communications?

Equipment Needed

AC10 drive, RS232 to RS485 converter, PDB.

IMAGE BROKEN -- DCLIFFEIMAGE BROKEN -- DCLIFFE

Procedure

  1. Connect RS485 converter.
    IMAGE BROKEN -- DCLIFFE
    NOTE: The 120 Ohm resistor must be removed to work with PDB but must be in to work with TS8000 (HMI) communications.
  2. Set up the computer's COM port.
    IMAGE BROKEN -- DCLIFFE

  3. Set PDB protocol.
    IMAGE BROKEN -- DCLIFFE
    IMAGE BROKEN -- DCLIFFE

  4. Set AC10 protocol.
    Parameter Description Setting Range Default
    F900 Communication Address 0: Broadcast Address
    1-255: Single Inverter Address
    1
    F901 Communication Mode 1: ASCII
    2: RTU
    2
    F902 *Stop Bits 0: None
    1: 1 Stop Bit
    2: 2 Stop Bits
    2
    F903 Parity Check 0: Invalid
    1: Odd
    2: Even
    1
    F904 Baud Rate (bps)
    9600 is recommended
    0: 1200
    1: 2400
    2: 4800
    3: 9600
    4: 19200
    5: 38400
    6: 57600
    3
    F905 Communication Time Out 0-3000 0

    *In the IP66 version, F902 is RESERVED

  5. AC10 Communication Settings
    Mode = RTU
    ASCII Mode
    Byte Function
    1 Start Bit (Low Level)
    7 Data Bit
    0/1 Parity Check Bit (None for this bit in case of no checking. Otherwise 1 bit)
    1/2 Stop Bit (1 bit in case of checking, otherwise 2 bits)

    RTU Mode
    Byte Function
    1 Start Bit (Low Level)
    8 Data Bit
    0/1 Parity Check Bit (None for this bit in case of no checking. Otherwise 1 bit)
    1/2 Stop Bit (1 bit in case of checking, otherwise 2 bits)

    Read Parameters, Write Commands, COM Parameters -- See Section 12 in AC10 Manual

PDB Program

IMAGE BROKEN -- DCLIFFE

Network Connection (2-wire)

IMAGE BROKEN -- DCLIFFE

3JAN2017 LS