Parker Hannifin
home | products | how to buy | support & downloads | literature | search

Click Here to go to new EM&D Knowledge Base (FAQ) site


What is the current overload rating for the AC890 drive?

  1. Frames B - D AC890 have an overload rating of 150% for 60 seconds.
  2. AC890 Frame sizes E and above have an overload rating of 150% for 60 seconds in Constant Torque and 110% for 60 seconds in Quadratic Torque.
  3. The AC890PX has an overload rating of 150% for 60 seconds in Constant Torque and 110% for 60 seconds in Quadratic Torque.

7NOV2016 LS